MCi Limited


»
about » products » approvals » order » contact » home



Standard Transformer Series: C-01/02 | C-03/04 | C-05 | C-06/07 | C-44 | C-49

Control Transformers | Speed Control Autotransformers | Elevator Coils | Custom Products

VDE PC Mount Transformers Series C-44: VDE PC Mount Transformers

CSA 4000-volt RMS Hipot, available in a variety of sizes. Insulation Class 130C. Available with either 115V or dual 115/230V primary. MCi's split bobbin and non-concentric winding provide better insulation and high isolation, thus eliminating the need for electro-static shielding. These transformers are designed to pass VDE's strict creepage distance requirements. Adaptations of standard transformers are also available. Dots on schematics shown below indicate like polarity.

Series C-44
Series C-44 Mounting Style A
Series C-44 Mounting Style B

Dimensions:

Transformer
VA
Schematic,
Mounting
Style

L
W
H
A
B
C
Pin
Size

MW
ML
Screw
Size

Max. No.
Term-
inals

LBS
C-44-3-_ _ _
2.5
1, A
1-5/8
1-7/16
1-1/8
.200
.250
1.000
.025 sq.
1-1/16
-
4
8
.25
C-44-4-_ _ _
5.0
1, A
1-5/8
1-7/16
1-3/8
.200
.400
1.000
.025 sq.
1-1/16
-
4
8
.37
C-44-5-_ _ _
10.0
1, A
1-7/8
1-9/16
1-3/8
.200
.400
1.140
.036 sq.
1-1/4
-
4
8
.53
C-44-6-_ _ _
20.0
2, A
2-1/4
1-7/8
1-5/8
.400
.400
1.460
.036 sq.
1-1/2
-
4
12
.90
C-44-7-_ _ _
30.0
2, B
2-5/8
2-3/16
1-9/16
.275
-
1.680
.045 sq.
1-3/4
2-3/16
6
12
1.15
C-44-8-_ _ _
56.0
2, B
3
2-1/2
1-13/16
.300
-
1.900
.045 sq.
2
2-1/2
6
12
1.70

Current Ratings (AMPS RMS):

Last 3 Digits of
Part Number:

010
012
016
020
024
028
036

SERIES CONNECTIONSECONDARY VOLTAGE
First 4 Digits:
10V
C.T.

12.6V
C.T.

16V
C.T.

20V
C.T.

24V
C.T.

28V
C.T.

36V
C.T.

C-44-3-_ _ _
.25
.20
.15
.12
.10
.09
.07
C-44-4-_ _ _
.50
.40
.31
.25
.21
.18
.14
C-44-5-_ _ _
1.00
.80
.62
.50
.42
.36
.28
C-44-6-_ _ _
2.00
1.60
1.25
1.00
.83
.72
.56
C-44-7-_ _ _
3.00
2.40
1.90
1.50
1.25
1.06
.82
C-44-8-_ _ _
5.60
4.40
3.50
2.80
2.33
2.00
1.56

PARALLEL CONNECTIONSECONDARY VOLTAGE
5V
6.3V
8V
10V
12V
14V
18V
C-44-3-_ _ _
.50
.40
.30
.24
.20
.18
.14
C-44-4-_ _ _
1.00
.80
.62
.50
.42
.36
.28
C-44-5-_ _ _
2.00
1.60
1.25
1.00
.84
.73
.56
C-44-6-_ _ _
4.00
3.20
2.50
2.00
1.66
1.44
1.12
C-44-7-_ _ _
6.00
4.80
3.80
3.00
2.50
2.12
1.64
C-44-8-_ _ _
11.20
8.80
7.00
5.60
4.66
4.00
3.12

Part Number Designation:

  1. Locate the column, in the table above, for the required voltage.
  2. In the voltage column, locate the required current reading.
  3. Moving left from the current reading, find the number indicating required primary - dual 115V/230V.
  4. Derive part number by combining digits indentifying required primary and digits at the top of column giving required voltage.